I had a problem with this 100A DC breaker, that was not handling 100A, but breaking the battery pack after all my Grid Tie Inverters would come on for few minutes producing 1000W all together
So we have 1000W produced and fed by into the Grid, plus some heat wasted for each GTI, let's say 200W (?) more, all this coming from the battery pack energy: 1200W / 24V = 50A
So this breaker was more like a 50A DC breaker in the end ....
So this breaker was more like a 50A DC breaker in the end ....
The not really 100A DC breaker
A real (I hope) 100A DC breaker from the Enginer Prius PHEV Kit
New position (on the floor) for this new breaker
A bar of copper is linking the bottom to top cells groups
With this new real 100A DC breaker, the ESS can hold the produced 1000W for long periods of time without any problem :-)